Chemical plants are generally prone to hazards. Hazards are chemical or
physical conditions that have the potential to cause damage to people, property
and the environment. The prevention of accidents through the use of appropriate
technologies to identify the hazards of a chemical plant and eliminate them
before an accident occurs is what safety is all about.
In the plant for manufacturing ethylene carbonate, the ethylene oxide
storage tank and external loop reactor are associated with lot of hazards.
Identification of hazards and eliminating them using proper safety measures is
mandatory.
14.1 Ethylene Oxide Storage Tank
Hazard Identifications and Safety Measures
14.1.1 Pressure build up in the tank leading to vapor
leak
If the inner walls of the tank surface are not clean, it may lead to
polymerisation reaction. These reactions get initiated at ambient temperature
by trace amount of iron dust. At high temperature, the reaction gets thermally initiated.
Since polymerisation reaction is highly exothermic, it is self accelerating and
can result in dangerous rise in pressure which leads to vaporization. High
pressure build up eventually leads to explosive decomposition. The storage tank is provided with a relief
system. Relief system consists of a network of components like pipe to relief,
the relief device, discharge pipelines, scrubber and flare. Pressure relief
devices are installed at points where upset conditions create pressures that
may exceed the Maximum Allowable Working Pressure (MAWP). Rupture discs are
provided with embedded wires that are cut when the disc ruptures that can
activate an alarm in the control room to alert the operator. Ethylene oxide
vapours are completely soluble in water. A packed scrubber column follows the
rupture disc. EO gets scrubbed with circulating water in the column. The
residual EO vapours proceed to a flaring system. The objective of a flare
system is to burn the toxic gas to produce combustion products that are neither
toxic nor combustible. Thus enough safety measures have been taken to eliminate
hazards due to pressure build up leading to vapour leak in storage tank.